Overview
Fluke 43B power analyser
* NiMH Battery provides extended operating time of 6.5 hours
* Combines the most useful capabilities of a power quality analyzer, multimeter and scope
* Calculates 3-phase power on balanced loads, from a single-phase measurement
* Trends voltage, current, frequency, power harmonics and captures voltage sags, transients and inrush current
* Monitoring functions help track intermittent problems and power system performance
* Records two selectable parameters for up to 16 days
* 20 measurement memories to save/recall screens and data with cursor readings
* FlukeView® software can log harmonics and all other readings over time and provides a complete harmonics profile up to the 51st harmonic
* Measures resistance, diode voltage drop, continuity, and capacitance
* Users/applications manual and power quality video to help answer tough questions
* Complete package with voltage probes and 400 A current clamp, FlukeView Software and optically isolated interface cable
* 3 year warranty on the Fluke 43B, 1 year on accessories
|
|
Description
Fluke 43B Power Quality Analyzer - Get control of power problems
The Fluke 43 Power Quality Analyzer performs the measurements you need to maintain power systems, troubleshoot power problems and diagnose equipment failures. All in a rugged handheld package.
What's Included?
C120 Hard Case
TP1 Flat-tipped Slim-Reach Test Probes
TP4 4 mm Round Slim-Reach Test Probes
i400s AC Current Clamp
OC4USB Optically Isolated USB Interface Adapter
BP120MH Rechargeable NiMH Battery Pack (installed)
PM 8907 Line Voltage Adapter/Battery Charger
SW43W FlukeView™ Power Quality Analyzer Software and Users Manual on CD-ROM
Shielded Banana-to-BNC Adapter
Users Manual / Application Guide

| Specifications |
| Input Characteristics |
| Input impedance |
1 MΩ, 20 pF |
| Voltage rating |
600V rms, CAT III |
|
| V/A/Hz Display |
| True-rms voltage (ac + dc) |
|
| Ranges: |
5.000 V, 50.00 V, 500.0 V, 1250 V* |
| Accuracy: |
±(1% + 10 counts) |
|
|
| True-rms current (ac + dc) |
|
| Ranges: |
50.00 A, 500.0 A, 5.000 kA, 50.00 kA, 1250 kA |
| Accuracy: |
±(1% + 10 counts) |
|
|
| Frequency |
|
| Ranges: |
10.0 to 15.0 kHz |
| Accuracy: |
± ([% of reading] + [counts]): 0.5% + 2 |
|
|
| CF Crest factor |
|
| Ranges: |
1.0 - 10.0 |
| Accuracy: |
±(5% + 1 count) |
|
| Power Display |
| Watts, VA, VAR |
|
|
1-phase and 3-phase,3 conductor balanced loads |
| Ranges: |
250 W - 1.56 GW |
| Accuracy: |
±(4% + 4 counts) Fundamental Power |
| Accuracy: |
± (2 % + 6 counts) Total Power |
|
|
| PF Power Factor |
|
| Range: |
0 - 1.0 |
| Accuracy: |
±0.04 |
| DPF Displacement Power Factor, Cos .F |
|
| Range: |
0.25 - 0.9 |
| Accuracy: |
±0.04 |
| Range: |
0.90 - 1.0 |
| Accuracy: |
±0.03 |
|
|
| H2 Frequency Fundamental |
|
| Ranges: |
40.0 to 70.0 Hz |
| Accuracy: |
± ([% of reading] + [counts]): 0.5% + 2 |
|
| Harmonics Display |
| Voltage, Current, Frequency |
|
| Ranges: |
Fundamental to 51st harmonic |
| Accuracy: |
|
| Fundamental: |
VA ±(3% + 2 counts) W ±(5% + 2 counts) |
| 2 to 31st harmonic: |
VA ±(5% +3 counts) W ±(10% +10 counts) |
| 32 to 51st harmonic: |
VA ±(15% +5 counts) W ±(30% +5 counts) |
|
|
| Frequency Fundamental |
|
| Ranges: |
40 Hz to 70 Hz |
| Accuracy: |
±0.25 Hz |
|
|
| Phase |
|
| Range: |
V, A (between Fundamental & Harmonics) |
| Accuracy: |
±3º to ±15º |
| Range: |
W (between Voltage Fundamental & Current Harmonics) |
| Accuracy: |
±5º to ±15º |
|
|
| K-factor (Current and Power) |
|
| Range: |
1.0 to 30.0 |
| Accuracy: |
±10% |
|
|
| THD Total Harmonic Distortion |
|
| Range: |
0.00 - 99.99 |
| Accuracy: |
±(3% + 8 counts) |
|
| Sags and Swells |
| Recording times: |
4 min to 16 days (selectable) |
| Vrms Actual, Vrms max, min(AC + DC) |
|
| Ranges: |
5.000V, 50.00V, 500.0V, 1250V* |
| Accuracy: |
Readings ±(2% +10 counts); Cursor readings ± (2% + 12 counts) |
|
|
| Arms Actual, Arms max, min (AC + DC) |
|
| Ranges: |
50.00A, 500.0A, 5.000 kA, 50.00 kA |
| Accuracy: |
±(2% +10 counts) |
|
| Transient Capture |
| Minimum pulse width: |
40 ns |
| Useful bandwidth input 1: |
DC to 1 MHz |
| Number of transients: |
40 |
| Voltage threshold settings: |
20%, 50%, 100%, 200% above or below reference |
| Reference signal: |
After START, the Vrms and frequency of the signal are measured. From these data a pure sinewave is calculated as reference for threshold setting. |
| Vpeak min, Vpeak max at cursor: |
10 V, 25 V, 50 V, 125 V, 250 V, 500 V, 1250 V Accuracy: ±5% of full scale |
|
| R, C, Diode, Continuity |
| Resistance ranges: |
500.0 Ω, 5.000 kΩ, 50.00 kΩ, 500.0 kΩ, 5.000 MΩ, 30.00 MΩ |
| Resistance accuracy: |
±(0.6% + 5 counts) |
| Capacitance ranges: |
50.00 nF, 500.0 nF, 5.000 µF, 50.00 µF, 500.0 µF |
| Capacitance accuracy: |
±(2% + 10 counts) |
| Diode Ranges: |
0 to 3.000 V |
| Diode voltage: |
|
| Accuracy: |
±(2% + 5 counts) |
| Continuity: |
Beeper on at < 30 Ω ± 5 Ω |
| Max current: |
0.5 mA |
| Temperature: |
°C or °F |
|
| Inrush Current |
| Inrush times: |
1 s, 5 s, 10 s, 50 s, 100 s, 5 min |
| Current ranges: |
1 A, 5 A, 10 A, 50 A, 100 A, 500 A, 1000 A |
| Cursor readings: |
A peak max at cursor 1 and cursor 2 |
| Accuracy: |
±5% of full scale |
| Time between cursors: |
4 to 235 pixels (1 pixel = inrush time/250) Accuracy: ±(0.2% + 2 pixels) |
|
| Temperature (with accessory) |
| Range: |
-100 °C - 400 °C |
| Accuracy: |
±(0.5% + 5 counts) |
|
| Scope Display |
| Measurements: |
dc, ac, ac+dc, peak, peak-peak, frequency, duty cycle, phase, pulse width, crest factor |
| Time ranges: |
20 ns/div to 60 s/div |
| Max sampling rate: |
25 MS/s |
| Bandwidth |
|
| Voltage channel [1]: |
20 MHz at inputs, 1 MHz with TL24 Leads |
| Current channel [2]: |
DC to 15 kHz at inputs, 10 kHz with i400s Current Clamp |
| Coupling: |
AC, DC (10 Hz - 3 dB) |
| Vertical sensitivity: |
5 mV/div to 500V/div |
| Vertical resolution: |
8 bit (256 levels) |
| Record length: |
512 samples per channel |
| Base ranges: |
60 S/div to 20 nS/div ± (0.4% + 1 pixel) |
| Timebase modes: |
Normal, roll, single |
| Pre-trigger: |
Up to 10 divisions |
| Trigger Source: |
Input 1 or Input 2 or automatic selection |
| Trigger Mode: |
Automatic Connect-and-View™, Free Run, and Single Shot |
|
|
| Connect-and-View™: |
Advanced automatic triggering that recognizes signal patterns |
|
Automatically adjusts triggering, timebase and amplitude and displays stable pictures |
|
| Memories |
|
20 (screens, settings, data) |
|
| Recording |
| Recording times: |
4 min to 16 days (selectable) |
| Parameters: |
Choose one or two parameters from one of the groups below: |
|
Volts/Ampères/Hertz |
| Power: |
Watts, VA, VAR, PF, DPF, Frequency |
|
Harmonics, THD, Volts (Fund. & Harmonic), Ampères (F&H) Watts(F&H) |
|
Frequency (H), %(H) of total, Phase(H), KF |
|
Temperature |
| Resistance: |
Resistance, Diode, Continuity, Capacitance |
| Scope: |
DC Voltage, DC Current, AC Voltage, AC Current, Frequency, |
|
Pulse Width + or -, Phase, Duty cycle + or -, Peak max, Peak min, Peak min-max, Crest Factor |
|
| Note |
|
*Rated EN 61010-1 600 V CAT III CSA |
|
Click here to download the Fluke 43B Data Sheet
|